ORDER NUMBER
R-14-20
IN THE MATTER OF
the Utilities Commission Act, RSBC 1996, Chapter 473
and
British Columbia Hydro and Power Authority
Mandatory Reliability Standard Assessment North American Electric Reliability Corporation
COVID-19 Compliance Response
BEFORE:
W. M. Everett, QC, Panel Chair
E. B. Lockhart, Commissioner
on July 29, 2020
ORDER
WHEREAS:
A.
On June 17, 2020, British Columbia Hydro and Power Authority (BC Hydro) submitted to the British Columbia
Utilities Commission (BCUC), its assessment of the proposed delayed effective dates for 14 Mandatory
Reliability Standards (MRS) identified by the North American Electric Reliability Corporation (NERC) in an
informational letter to the BCUC dated April 24, 2020 (NERC Letter) (Report). In the Report, and after
receiving feed back from participating Entities, BC Hydro recommends delaying the effective dates for six of
the 14 MRS that currently have implementation dates in British Columbia in the second half of 2020, due to
the impacts of the COVID-19 pandemic;
B.
Pursuant to section 125.2 of the Utilities Commission Act (UCA) the BCUC has exclusive jurisdiction to
determine whether a “reliability standard” as defined in the UCA, is in the public interest and should be
adopted in British Columbia (BC). The UCA also states BC Hydro must review each reliability standard and
provide a report to the BCUC assessing each reliability standard for its reliability impact, suitability,
applicability and potential cost of adoption. Within this process, BC Hydro also recommends effective dates
for the MRS brought before the BCUC for adoption;
C.
On March 18, 2020, the United States (US) Federal Energy Regulatory Commission (FERC) and NERC
provided industry guidance to ensure grid reliability amid potential COVID-19 impacts (Guidance);
D.
On March 19, 2020, the BCUC issued Letter L-11-20 to all Entities registered with the British Columbia
Mandatory Reliability Standards Program (MRS Program), advising that the BCUC is using regulatory
discretion that aligns with measures in the Guidance. In Letter L-11-20, the BCUC also stated that it will
consider the impact of the COVID-19 pandemic for specific aspects of compliance with MRS and included
Direction to ensure Bulk Electric System (BES) reliability amid potential COVID-19 impacts and related
compliance with MRS;
Final Order
1 of 3
Order R-14-20
E.
On April 6, 2020, NERC filed a motion with FERC to defer the implementation, by three to six months, of 14
reliability standards scheduled to become effective in the US, in whole or in part, during the second half of
2020 (Motion). FERC granted that Motion on April 17, 2020;
F.
In the NERC Letter, NERC indicated registered entities in the US were granted deferral of three to six months
for reliability standards with implementation dates scheduled to become effective in the US in the second
half of 2020 and suggested the BCUC also consider a three to six month delay for 14 MRS scheduled to go
into effect in the second half of 2020 in BC;
G.
Aware of the Motion and in connection with the NERC Letter, and in consideration of its responsibilities
outlined in the UCA to assess reliability standards including effective dates in BC, BC Hydro sent a request for
feedback to Registered Entities in the MRS Program requesting comments on the deferral of effective dates
of the 14 MRS identified in the NERC Letter;
H.
Eight Registered Entities responded to BC Hydro’s request for feedback. Three Registered Entities responded
stating no extensions were required. Five of the Registered Entities stated a six-month implementation
extension is required for three MRS due to on site restrictions for contractors. Additionally, BC Hydro stated
a six-month implementation extension is required for three other MRS due to on site restrictions for control
centres;
I.
By Order R-13-20, dated July 2, 2020, BC Hydro was directed to publish a notice of process for consideration
of the delayed effective dates along with the established Regulatory Timetable for written public comment;
J.
On July 9, 2020, Dokie General Partnership, Innergex Renewable Energy Inc., Jimmie Creek Limited
Partnership, Toba Montrose General Partnership and Upper Lillooet River Power LP submitted that their
comments are represented in the Report and stated their support of the conclusion and recommendations
as presented by BC Hydro in the Report;
K.
On July 10, 2020, FortisBC Inc. submitted it has no additional comments regarding the Report;
L.
On July 14, 2020, BC Hydro submitted a response to the written public comments and has no further reply
comments; and
M. The BCUC has reviewed and considered the Report and the proposed delayed effective dates assessed
therein, as well as comments received from Entities and considers that the delayed effective date of six MRS
is warranted.
NOW THEREFORE pursuant to sections 58 to 61 of the UCA, the BCUC orders as follows:
1.
Six of the fourteen MRS in the Report, and previously adopted in BC, have revised effective dates as
identified in Attachment A to this order.
2.
All reliability standards listed in Attachment B to this order are effective as of the dates shown. The effective
dates for the reliability standards listed in Attachment B supersede the effective dates that were included in
any similar list appended to any previous order of the BCUC.
Final Order
2 of 3
Order R-14-20
DATED at the City of Vancouver, in the Province of British Columbia, this 29th day of July 2020.
BY ORDER
Original Signed By:
W. M. Everett, QC
Commissioner
Attachment
Final Order
3 of 3
ATTACHMENT A
to Order R-14-20
British Columbia Utilities Commission
Reliability Standard Effective Dates as Revised by this Order
Table 1 British Columbia Utilities Commission Reliability Standards with Effective Dates as Adopted
Effective Date(s) as Adopted by
Approved New Effective Date(s) as
Standard
Standard Name
Previous Orders
per this Order
1.
CIP-010-2 R3.2,
Cyber Security –
October 1, 2020
N/A
R3.2.1 and
Configuration Change
R3.2.2
Management and
Vulnerability Assessments
2.
EOP-004-4
Event Reporting
October 1, 2020
N/A
3.
EOP-005-3
System Restoration and
October 1, 2020
N/A
Blackstart Resources
4.
EOP-006-3
System Restoration
October 1, 2020
N/A
Coordination
5.
EOP-008-2
Loss of Control Center
October 1, 2020
N/A
Functionality
6.
IRO-017-1
Outage Coordination
October 1, 2020
N/A
7.
MOD-025-2
Verification and Data
40% compliance by October 1, 2017
40% compliance by October 1, 2017
Reporting of Generator Real
60% compliance by October 1, 2018
60% compliance by October 1, 2018
and Reactive Power
80% compliance by October 1, 2019
80% compliance by October 1, 2019
Capability and Synchronous
100% compliance by October 1, 2020
100% compliance by April 1, 2021
Condenser Reactive Power
Capability
8.
PRC-19-2
Coordination of Generating
40% compliance by October 1, 2017
40% compliance by October 1, 2017
Unit or Plant Capabilities,
60% compliance by October 1, 2018
60% compliance by October 1, 2018
Voltage Regulating Controls,
80% compliance by October 1, 2019
80% compliance by October 1, 2019
and Protection
100% compliance by October 1, 2020
100% compliance by April 1, 2021
9.
PRC-024-2
Generator Frequency and
40% compliance by October 1, 2017
40% compliance by October 1, 2017
Voltage Protective Relay
60% compliance by October 1, 2018
60% compliance by October 1, 2018
Settings
80% compliance by October 1, 2019
80% compliance by October 1, 2019
100% compliance by October 1, 2020
100% compliance by April 1, 2021
10.
TOP-001-4
Transmission Operations
October 1, 2020
April 1, 2021
11.
TOP-002-4
Transmission Operations
October 1, 2020
April 1, 2021
12.
TOP-010-1(i)
Real-time Reliability
October 1, 2020
April 1, 2021
Monitoring and Analysis
Capabilities
13.
TPL-001-4 R2-
Transmission Operations
July 1, 2020
N/A
R6, R8
14.
VAR-501-
Power System Stabilizer (PSS)
October 1, 2020
N/A
WECC-1
1 of 1
British Columbia Utitlies Commission
Reliability Standards with Effective Dates adopted in British Columbia
Standard
Name
BAL-001-2
Real Power Balancing Control
Performance
BAL-002-2
1
Disturbance Control Standard –
Contingency Reserve for
Recovery from a Balancing
Contingency Event
BAL-002-3
Disturbance Control Standard –
Contingency Reserve for
Recovery from a Balancing
Contingency Event
BAL-002-WECC-2a
Contingency Reserve
BAL-003-1.1
Frequency Response and
Frequency Bias Setting
BAL-004-WECC-2
1
Automatic Time Error
Correction
BAL-004-WECC-3
Automatic Time Error
Correction
BAL-005-0.2b
1
Automatic Generation Control
BAL-005-1
Balancing Authority Control
CIP-002-5.1a
Cyber Security — BES Cyber
System Categorization
CIP-003-7
1
Cyber Security — Security
Management Controls
CIP-003-8
Cyber Security — Security
Management Controls
CIP-004-6
Cyber Security — Personnel &
Training
1
Reliability standard is superseded by the revised/replacement reliability standard listed immediately below it as of the
effective date(s) of the revised/replacement reliability standard.
2
On November 21, 2013, FERC Order 788 (referred to as Paragraph 81) approved the retiring of the reliability standard
requirements.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-14-16
July 1, 2016
R-39-17
January 1, 2018
R-21-19
April 1, 2020
R-39-17
July 26, 2017
R-32-16A
October 1, 2016
R-32-14
October 1, 2014
R-21-19
January 1, 2020
R-41-13
December 12, 2013
R2: Retired
January 21, 2014
2
R-33-18
October 1, 2019
R-33-18
October 1, 2018 and as
per B.C.-specific
Implementation Plan
R-21-19
October 1, 2019 and as
per B.C.-specific
Implementation Plan
N/A
Pending BCUC review
R-39-17
October 1, 2018 and as
per B.C.-specific
Implementation Plan
1 of 20
Standard
Name
CIP-005-5
1
Cyber Security – Electronic
Security Perimeter(s)
CIP-005-6
Cyber Security – Electronic
Security Perimeter(s)
CIP-006-6
Cyber Security — Physical
Security of BES Cyber Systems
CIP-007-6
Cyber Security — System
Security Management
CIP-008-5
1
Cyber Security – Incident
Reporting and Response
Planning
CIP-008-6
Cyber Security – Incident
Reporting and Response
Planning
CIP-009-6
Cyber Security — Recovery
Plans for BES Cyber Systems
CIP-010-2
1
Cyber Security – Configuration
Change Management and
Vulnerability Assessments
CIP-010-3
Cyber Security – Configuration
Change Management and
Vulnerability Assessments
CIP-011-2
Cyber Security – Information
Protection
CIP-013-1
Cyber Security - Supply Chain
Risk Management
CIP-014-2
Physical Security
COM-001-3
Communications
COM-002-4
Operating Personnel
Communications Protocols
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-38-15
October 1, 2018 and as
per B.C.-specific
Implementation Plan
N/A
Pending BCUC review
R-39-17
October 1, 2018 and as
per B.C.-specific
Implementation Plan
R-39-17
October 1, 2018 and as
per B.C.-specific
Implementation Plan
R-38-15
October 1, 2018 and as
per B.C.-specific
Implementation Plan
N/A
Pending BCUC review
R-39-17
October 1, 2018 and as
per B.C.-specific
Implementation Plan
R-39-17
October 1, 2018 and as
per B.C.-specific
Implementation Plan
N/A
Pending BCUC review
R-39-17
October 1, 2018 and as
per B.C.-specific
Implementation Plan
N/A
Pending BCUC review
R-32-16A
October 1, 2017 and as
per B.C.-specific
Implementation Plan
R-39-17
R1, R2: October 1, 2017
R3-R13: October 1, 2018
R-32-16A
April 1, 2017
2 of 20
Standard
Name
EOP-003-1
3
Load Shedding Plans
EOP-003-2
4
Load Shedding Plans
EOP-004-3
1
Event Reporting
EOP-004-4
Event Reporting
EOP-005-2
1
System Restoration and
Blackstart Resources
EOP-005-3
System Restoration and
Blackstart Resources
EOP-006-2
1
System Restoration
Coordination
EOP-006-3
System Restoration
Coordination
EOP-008-1
1
Loss of Control Center
Functionality
EOP-008-2
Loss of Control Center
Functinality
EOP-010-1
6
Geomagnetic Disturbance
Operations
EOP-011-1
Emergency Operations
FAC-001-2
1
Facility Interconnection
Requirements
FAC-001-3
Facility Interconnection
Requirements
FAC-002-2
Facility Interconnection Studies
FAC-003-4
Transmission Vegetation
Management
3
Reliability standard would be superseded by EOP-003-2 if adopted in B.C. Adoption of EOP-003-2 pending
reassessment.
4
Reliability standard is superseded by EOP-011-1 as of the EOP-011-1 effective date in conjunction with PRC-010-2
Requirement 1 if adopted in B.C. Adoption of PRC-010-2 pending reassessment.
5
Unable to assess based on undefined Planning Coordinator/Planning Authority footprints and entities responsible. The
BCUC Reasons for Decision for Order No. R-41-13 (page 20), indicated that a separate process would be established to
consider this matter as it pertains to B.C.
6
Requirement 2 of the reliability standard will be effective upon the retirement of IRO-005-3.1a Requirement 3 which
follows the effective date of IRO-002-4 (October 1, 2017; per BCUC Order No. R-39-17).
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
G-67-09
November 1, 2010
n/a
Adoption held in abeyance
at this time
5
R-39-17
October 1, 2017
R-21-19
October 1, 2020
R-32-14
August 1, 2015
R3.1: Retired
January 21, 2014
2
R-21-19
October 1, 2020
R-32-14
August 1, 2014
R-21-19
October 1, 2020
R-32-14
August 1, 2015
R-21-19
October 1, 2020
R-38-15
R1, R3: October 1, 2016
R2: At retirement of
IRO-005-3.1a R3
R-39-17
October 1, 2018
R-38-15
October 1, 2016
R-33-18
October 1, 2019
R-38-15
October 1, 2015
R-39-17
October 1, 2017
3 of 20
Standard
Name
FAC-008-3
Facility Ratings
FAC-010-3
System Operating Limits
Methodology for the Planning
Horizon
FAC-011-3
System Operating Limits
Methodology for the
Operations Horizon
FAC-013-1
7
Establish and Communicate
Transfer Capability
FAC-013-2
Assessment of Transfer
Capability
for the Near-Term Transmission
Planning Horizon
FAC-014-2
Establish and Communicate
System Operating Limits
FAC-501-WECC-1
1
Transmission Maintenance
FAC-501-WECC-2
Transmission Maintenance
INT-004-3.1
Dynamic Transfers
INT-006-4
Evaluation of Interchange
Transactions
INT-009-2.1
Implementation of Interchange
INT-010-2.1
Interchange Initiation and
Modification for Reliability
INT-011-1.1
Intra-Balancing Authority
Transaction Identification
IRO-001-4
Reliability Coordination –
Responsibilities
IRO-002-2
8
Reliability Coordination –
Facilities
IRO-002-5
1
Reliability Coordination –
Monitoring and Analysis
IRO-002-6
Reliability Coordination –
Monitoring and Analysis
7
Reliability standard would be superseded by the FAC-013-2 if adopted in B.C. Adoption of FAC-013-2 pending
reassessment.
8
Refer to “IRO and TOP Reliability Standards Supersession Mapping” section below.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-32-14
August 1, 2015
R4 and R5: Retired
January 21, 2014
2
R-39-17
R1–R4: October 1, 2017
R5: Retired
R-39-17
October 1, 2017
G-67-09
November 1, 2010
n/a
Adoption held in abeyance
at this time
5
G-167-10
January 1, 2011
R-1-13
April 15, 2013
R-21-19
October 1, 2019
R-38-15
R1, R2: October 1, 2015
R3: January 1, 2016
R-38-15
October 1, 2015
R-38-15
October 1, 2015
R-38-15
October 1, 2015
R-38-15
October 1, 2015
R-39-17
October 1, 2017
R-1-13
April 15, 2013
R-33-18
January 1, 2019
N/A
Pending BCUC review
4 of 20
Standard
Name
IRO-005-3.1a
8,9
Reliability
Coordination - Current Day
Operations
IRO-006-5
Reliability Coordination –
Transmission Loading Relief
IRO-006-WECC-2
1
Qualified Transfer Path
Unscheduled Flow (USF) Relief
IRO-006-WECC-3
Qualified Transfer Path
Unscheduled Flow (USF) Relief
IRO-008-2
Reliability Coordinator
Operational Analyses and
Real-time Assessments
IRO-009-2
Reliability Coordinator Actions
to Operate Within IROLs
IRO-010-2
Reliability Coordinator Data
Specification and Collection
IRO-014-3
Coordination Among Reliability
Coordinators
IRO-015-1
8
Notification and Information
Exchange
IRO-017-1
Outage Coordination
IRO-018-1
1
Reliability Coordinator
Real-time Reliability Monitoring
and Analysis Capabilities
IRO-018-1(i)
Reliability Coordinator
Real-time Reliability Monitoring
and Analysis Capabilities
MOD-001-1a
Available Transmission System
Capability
MOD-004-1
Capacity Benefit Margin
MOD-008-1
Transmission Reliability Margin
Calculation Methodology
9
Requirement 3 of the reliability standard is superseded by EOP-010-1 Requirement 2 as of the IRO-002-4 effective date
(October 1, 2017; per BCUC Order No. R-39-17).
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-32-14
August 1, 2014
R-1-13
April 15, 2013
R-38-15
October 1, 2015
N/A
Pending BCUC review
R-39-17
October 1, 2017
R-39-17
October 1, 2017
R-39-17
April 1, 2019
R-39-17
October 1, 2017
G-67-09
November 1, 2010
R-39-17
October 1, 2020
R-39-17
April 1, 2018
R-33-18
April 1, 2020
G-175-11
November 30, 2011
G-175-11
November 30, 2011
G-175-11
November 30, 2011
5 of 20
Standard
Name
MOD-010-0
10
Steady-State Data for Modeling
and Simulation for the
Interconnected Transmission
System
MOD-012-0
10
Dynamics Data for Modeling
and Simulation of the
Interconnected Transmission
System
MOD-020-0
Providing Interruptible
Demands and Direct Control
Load management Data to
System Operators and
Reliability Coordinators
MOD-025-2
Verification and Data Reporting
of Generator Real and Reactive
Power Capability and
Synchronous Condenser
Reactive Power Capability
MOD-026-1
Verification of Models and Data
for Generator Excitation Control
System or Plant Volt/Var
Control Functions
MOD-027-1
Verification of Models and Data
for Turbine/Governor and Load
Control or Active
Power/Frequency Control
Functions
MOD-028-2
Area Interchange Methodology
MOD-029-2a
Rated System Path
Methodology
MOD-030-3
Flowgate Methodology
MOD-031-2
Demand and Energy Data
MOD-032-1
Data for Power System
Modeling and Analysis
10
Reliability standard will be superseded by MOD-032-1 and MOD-033-1 if adopted in B.C. Adoption of MOD-032-1 and
MOD-033-1 pending reassessment.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
G-67-09
November 1, 2010
G-67-09
November 1, 2010
G-67-09
November 1, 2010
R-38-15
40% by October 1, 2017
With revised
60% by October 1, 2018
effective dates by
80% by October 1, 2019
Order R-14-20
100% by April 1, 2021
R-38-15
R1: October 1, 2016
R2: 30% by October 1,
2019
50% by October 1, 2021
100% by October 1, 2025
R3-R6: October 1, 2015
R-38-15
R1: October 1, 2016
R2: 30% by October 1,
2019
50% by October 1, 2021
100% by October 1, 2025
R3-R5: October 1, 2015
R-32-14
August 1, 2014
R-39-17
October 1, 2017
R-39-17
October 1, 2017
R-39-17
April 1, 2018
R-38-15
Effective date held in
abeyance
5
6 of 20
Standard
Name
MOD-033-1
Steady-State and Dynamic
System Model Validation
NUC-001-3
Nuclear Plant Interface
Coordination
PER-001-0.2
8
Operating Personnel
Responsibility and Authority
PER-002-0
Operating Personnel Training
PER-003-1
1
Operating Personnel Credentials
PER-003-2
Operating Personnel Credentials
PER-004-2
11
Reliability Coordination –
Staffing
PER-005-2
Operations Personnel Training
PER-006-1
12
Specific Training for Personnel
PRC-001-1.1(ii)
13
System Protection Coordination
PRC-002-2
Disturbance Monitoring and
Reporting Requirements
PRC-004-5(i)
Protection System Misoperation
Identification and Correction
PRC-004-WECC-2
Protection System and Remedial
Action Scheme Misoperation
PRC-005-1.1b
1,
16
Transmission and Generation
Protection System Maintenance
and Testing
PRC-005-2
1
Protection System Maintenance
11
Reliability standard will be superseded by PER-003-2 if adopted in B.C. as of the PER-003-2 effective date.
12
Reliability standard will supersede PRC-001-1.1(ii) R1 as of the effective date of PER-006-1.
13
PRC-001-1.1(ii) Requirement 1 will be superseded by PER-006-1 as of the effective date of PER-006-1; PRC-001-1(ii)
Requirements 3 and 4 will be superseded by PRC-027-1 as of the effective date of PRC-027-1; and, the rest of
PRC-001-1.1(ii) will be superseded by other reliability standards as of October 1, 2020.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-38-15
Effective date held in
abeyance
5
R-38-15
January 1, 2016
R-41-13
December 12, 2013
G-67-09
November 1, 2010
R-41-13
January 1, 2015
R-21-19
April 1, 2020
R-1-13
January 15, 2013
R-38-15
R1-R4, R6: October 1,
2016
R5: October 1, 2017
R-21-19
October 1, 2021
R-32-16A
October 1, 2016
R-32-16A
R1, R5: April 1, 2017
R2-R4, R6-R11: staged as
per B.C.-specific
Implementation Plan
R12: July 1, 2017
R-32-16A
October 1, 2017
R-39-17
October 1, 2017
Retired: Pending BCUC
Review
R-32-14
January 1, 2015
R-38-15
R1, R2, R5: October 1,
2017
R3, R4: staged as per
B.C.-specific
Implementation Plan
7 of 20
Standard
Name
PRC-005-2(i)
1
Protection System
Maintenance
PRC-005-6
Protection System, Automatic
Reclosing, and Sudden Pressure
Relaying Maintenance
PRC-006-3
14
Automatic Underfrequency
Load Shedding
PRC-007-0
15
Assuring consistency of entity
Underfrequency Load Shedding
Program Requirements
PRC-008-0
16
Implementation and
Documentation of
Underfrequency Load Shedding
Equipment Maintenance
Program
PRC-009-0
15
Analysis and Documentation of
Underfrequency Load Shedding
Performance Following an
Underfrequency Event
PRC-010-0
1
Technical Assessment of the
Design and Effectiveness of
Undervoltage Load Shedding
Program
PRC-010-2
Under Voltage Load Shedding
PRC-011-0
16
Undervoltage Load Shedding
system Maintenance and
Testing
14
Reliability standard supersedes PRC-006-1 and PRC-006-2 which have both been held in abeyance due to the undefined
Planning Coordinator/Planning Authority footprints and entities responsible.
15
Reliability standard will be superseded by PRC-006-3 if adopted in B.C. Adoption of PRC-006-3 pending reassessment.
16
Reliability standard is superseded by PRC-005-6 as per the PRC-005-6 B.C.-specific Implementation Plan.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-32-16A
R1, R2, R5: October 1,
2017
R3, R4: staged as per
B.C.-specific
Implementation Plan
R-39-17
R1, R2, R5: October 1,
2019
R3, R4: See
Implementation Plan
n/a
Adoption held in abeyance
at this time
5
G-67-09
November 1, 2010
G-67-09
November 1, 2010
G-67-09
November 1, 2010
G-67-09
November 1, 2010
R2: Retired
January 21, 2014
2
n/a
Adoption held in abeyance
at this time
5
G-67-09
November 1, 2010
8 of 20
Standard
Name
PRC-012-2
Remedial Action Schemes
PRC-015-1
17
Remedial Action Scheme Data
and Documentation
PRC-016-1
17
Remedial Action Scheme
Misoperations
PRC-017-1
16
Remedial Action Scheme
Maintenance and Testing
PRC-018-1
18
Disturbance Monitoring
Equipment Installation and Data
Reporting
PRC-019-2
Coordination of Generating Unit
or Plant Capabilities, Voltage
Regulating Controls, and
Protection
PRC-021-1
19
Under Voltage Load Shedding
Program Data
PRC-022-1
19
Under Voltage Load Shedding
Program Performance
17
Reliability standard is superseded by PRC-012-2 as of the PRC-012-2 effective date.
18
Reliability standard is superseded by PRC-002-2 as of the PRC-002-2 effective date.
19
Reliability standard is superseded by PRC‐010‐2 if adopted in B.C. Adoption of PRC-010-2 pending reassessment.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-33-18
October 1, 2021
R1: Attachment 1,
Section II Parts 6(d) and
6(e) to be determined.
Unable to be assessed at
this time.
5
R2: Attachment 2,
Section I Parts 7(d) and
7(e) to be determined.
Unable to be assessed at
this time.
5
R4: To be determined.
Unable to be assessed at
this time.
5
R-39-17
October 1, 2017
R-39-17
October 1, 2017
R-39-17
October 1, 2017
G-67-09
November 1, 2010
R-32-16A
40% by October 1, 2017
With revised
60% by October 1, 2018
effective dates by
80% by October 1, 2019
Order R-14-20
100% by April 1, 2021
G-67-09
November 1, 2010
G-67-09
November 1, 2010
R2: Retired
January 21, 2014
2
9 of 20
ATTACHMENT B
to Order R-14-20
BCUC Order
Standard
Name
Effective Date
Adopting
PRC-023-2
1, 20
Transmission Relay Loadability
R-41-13
R1-R5:
For circuits identified by
sections 4.2.1.1 and
4.2.1.4:
January 1, 2016
For circuits identified by
sections 4.2.1.2, 4.2.1.3,
4.2.1.5, and 4.2.1.6:
To be determined
5
R6: To be determined
5
PRC-023-4
Transmission Relay Loadability
R-39-17
R1-R5 Circuits 4.2.1.1,
4.2.1.4:
October 1, 2017 with the
exception of Criterion 6 of R1
which will not become
effective until
PRC-025-1 R1 is completely
effective in B.C. Until then,
PRC-023-2 R1,
Criterion 6 will remain in
effect.
R1-R5 Circuits 4.2.1.2,
4.2.1.3, 4.2.1.5,
4.2.1.6 and R6: To be
determined
PRC-024-2
Generator Frequency and Voltage
R-32-16A
40% by October 1, 2017
Protective Relay Settings
With revised
60% by October 1, 2018
effective dates by
80% by October 1, 2019
Order R-14-20
100% by April 1, 2021
PRC-025-1
1
Generator Relay Loadability
R-38-15
40% by October 1, 2017
60% by October 1, 2018
80% by October 1, 2019
100% by October 1, 2020
PRC-025-2
Generator Relay Loadability
R-21-19
October 1, 2019
PRC-026-1
Relay Performance During
n/a
Adoption held in abeyance
Stable Power Swings
at this time
5
PRC-027-1
21
Coordination of Protection
R-21-19
October 1, 2021
Systems for Performance During
Faults
20
PRC-023-2 Requirement 1, Criterion 6 only is superseded by PRC-025-1 as of PRC-025-1’s 100 per cent Effective Date.
21
Reliability standard will supersede PRC-001-1.1(ii) Requirements 3 and 4 as of the effective date of PRC-027-1.
10 of 20
Standard
Name
TOP-001-1a
8
Reliability Responsibilities and
Authorities
TOP-001-4
Transmission Operations
TOP-002-2.1b
8
Normal Operations Planning
TOP-002-4
Operations Planning
TOP-003-1
8
Planned Outage Coordination
TOP-003-3
Operational Reliability Data
TOP-004-2
8
Transmission Operations
TOP-005-2a
8
Operational Reliability
Information
TOP-006-2
8
Monitoring System Conditions
TOP-007-0
8
Reporting System Operating
Unit (SOL) and Interconnection
Reliability Operating Limit
(IROL) Violations
TOP-008-1
8
Response to Transmission Limit
Violations
TOP-010-1(i)
Real-time Reliability Monitoring
and Analysis Capabilities
TPL-001-0.1
22
System Performance Under
Normal (No Contingency)
Conditions (Category A)
TPL-001-4
Transmission System Planning
Performance Requirements
TPL-002-0b
22
System Performance Following
Loss of a Single Bulk Electric
System Element (Category B)
22
Reliability standard is superseded by TPL-001-4 Requirements 2 to 6, and 8 as of their effective dates.
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-1-13
January 15, 2013
R-33-18
April 1, 2021
With revised
effective dates by
Order R-14-20
R-41-13
December 12, 2013
R-39-17
April 1, 2021
With revised
effective dates by
Order R-14-20
R-1-13
April 15, 2013
R-39-17
April 1, 2019
G-167-10
January 1, 2011
R-1-13
April 15, 2013
R-1-13
April 15, 2013
G-67-09
November 1, 2010
G-67-09
November 1, 2010
R-33-18
April 1, 2021
With revised
effective dates by
Order R-14-20
G-167-10
January 1, 2011
R-27-18A
R1: July 1, 2019
R2-R6, R8: July 1, 2020
R7: To be determined
5
R-1-13
January 15, 2013
11 of 20
Standard
Name
TPL-003-0b
22
System Performance Following
Loss of Two or More Bulk
Electric System Elements
(Category C)
TPL-004-0a
22
System Performance Following
Extreme Events Resulting in the
Loss of Two or More Bulk
Electric System Elements
(Category D)
TPL-007-1
1
Transmission System Planned
Performance for Geomagnetic
Disturbance Events
TPL-007-3
Transmission System Planned
Performance for Geomagnetic
Disturbance Events
VAR-001-4.2
1
Voltage and Reactive Control
VAR-001-5
Voltage and Reactive Control
VAR-002-4.1
Generator Operation for
Maintaining Network Voltage
Schedules
VAR-501-WECC-2
1
Power System Stabilizer (PSS)
VAR-501-WECC-3.1
Power System Stabilizer (PSS)
ATTACHMENT B
to Order R-14-20
BCUC Order
Effective Date
Adopting
R-32-14
August 1, 2014
R-32-14
August 1, 2014
N/A
Adoption held in abeyance
at this time
5
N/A
Pending BCUC review
R-33-18
October 1, 2018
R-21-19
October 1, 2019
R-33-18
October 1, 2018
R-32-16A
October 1, 2016
R-33-18
October 1, 2020
R3: For units placed into
service after the effective
date: January 1, 2021
For units placed into
service pior the effective
date: January 1, 2024
12 of 20
ATTACHMENT B
to Order R-14-20
British Columbia Utilities Commission
IRO and TOP Reliability Standards
Supersession Mapping
This following mapping shows the supersession of Requirements for the following IRO, TOP, and PER reliability
standards by the revised/replacement IRO and TOP reliability standards adopted or yet to be adopted in B.C. as of
the effective date in the “B.C. Reliability Standards” section above:
IRO-002-2
—
Reliability Coordination - Facilities
IRO-005-3.1a
—
Reliability Coordination - Current Day Operations
IRO-015-1
—
Notifications and Information Exchange Between Reliability Coordinators
PER-001-0.2
—
Operating Personnel Responsibility and Authority
TOP-001-1a
—
Reliability Responsibilities and Authorities
TOP-002-2.1b —
Normal Operations Planning
TOP-003-1
—
Planned Outage Coordination
TOP-004-2
—
Transmission Operations
TOP-005-2a
—
Operational Reliability Information
TOP-006-2
—
Monitoring System Conditions
TOP-007-0
—
Reporting System Operating Limit (SOL) and Interconnection Reliability Operating
Limit (IROL) Violations
TOP-008-1
—
Response to Transmission Limit Violations
Standard IRO-002-2 — Reliability Coordination – Facilities
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirements R1, R3-R5, R7, and R8
IRO-002-4
Requirement R2
IRO-010-2
Requirement R6
IRO-008-2
Standard IRO-005-3.1a — Reliability Coordination - Current Day Operations
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirements R1-R3
IRO-002-4
Requirement R4
IRO-008-2
13 of 20
ATTACHMENT B
to Order R-14-20
Standard IRO-005-3.1a — Reliability Coordination - Current Day Operations
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirements R5 and R8
IRO-001-4
IRO-002-4
Requirements R6 and R7
IRO-008-2
IRO-017-1
Requirement R8
IRO-001-4
IRO-002-4
Requirement R9
IRO-002-4
IRO-010-2
Requirement R10
IRO-009-1
TOP-001-4
Requirement R11
MOD-001-2, Requirement R2 (pending FERC adoption in
the U.S. and subsequent assessment and adoption in B.C.)
Requirement R12
IRO-008-2
Standard IRO-015-1 — Notifications and Information Exchange Between Reliability Coordinators
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirements R1 and R2
IRO-014-3
Requirement R3
IRO-010-2
14 of 20
ATTACHMENT B
to Order R-14-20
Standard PER-001-0.2 — Operating Personnel Responsibility and Authority
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
All Requirements
TOP-001-4
Standard TOP-001-1a — Reliability Responsibilities and Authorities
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirements R1, R2, R4, R5, R6
TOP-001-4
Requirement R3
IRO-001-4
TOP-001-4
Requirement R7
TOP-001-4
TOP-003-3
IRO-010-2
Requirement R8
EOP-003-2, Requirement 1 (adoption held in abeyance in
B.C. due to PA/PC dependencies)
IRO-009-2
15 of 20
ATTACHMENT B
to Order R-14-20
Standard TOP-002-2.1b — Normal Operations Planning
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R1
TOP-001-4
TOP-002-4
Requirements R2, R5-R9, R12
TOP-002-4
Requirement R3
IRO-017-1
TOP-003-3
Requirement R4
IRO-017-1
IRO-008-2
Requirement R10
IRO-017-1
TOP-001-4
TOP-002-4
TOP-003-3
Requirement R11
TOP-001-4
TOP-002-4
Requirement R13
TOP-001-4
TOP-003-3
Requirements R14, R15, and R19
TOP-003-3
Requirements R16, R17, and R18
IRO-010-2
16 of 20
ATTACHMENT B
to Order R-14-20
Standard TOP-003-1 — Planned Outage Coordination
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R1
IRO-010-2
TOP-003-3
Requirement R2
IRO-017-1
TOP-003-3
Requirement R3
TOP-001-4
Requirement R4
IRO-008-2
IRO-017-1
Standard TOP-004-2 — Transmission Operations
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R1
TOP-001-4
Requirement R2
TOP-001-4
TOP-002-4
Requirements R3 and R4
TOP-001-4
Requirement R5
Retired
Requirement R6
IRO-017-1
TOP-001-4
17 of 20
ATTACHMENT B
to Order R-14-20
Standard TOP-005-2a — Operational Reliability Information
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R1
IRO-010-2
TOP-003-3
Requirement R2
TOP-003-3
Requirement R3
Retired
Standard TOP-006-2 — Monitoring System Conditions
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R1
IRO-010-2
TOP-001-4
TOP-003-3
Requirement R2
IRO-002-4
TOP-001-4
Requirement R3
IRO-010-2
TOP-003-3
Requirement R4
TOP-003-3
Requirement R5
IRO-002-5
TOP-001-4
Requirement R6
TOP-003-3
18 of 20
ATTACHMENT B
to Order R-14-20
Standard TOP-006-2 — Monitoring System Conditions
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R7
IRO-002-5
TOP-001-4
Standard TOP-007-0 — Reporting System Operating Limit (SOL) and Interconnection Reliability Operating Limit
(IROL) Violations
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirement R1
IRO-008-2
TOP-001-4
Requirement R2
IRO-009-2
TOP-001-4
Requirement R3
EOP-003-2, Requirement 1 (adoption held in abeyance in
B.C. due to PA/PC dependencies)
IRO-009-2
Requirement R4
IRO-008-2
19 of 20
ATTACHMENT B
to Order R-14-20
Standard TOP-008-1 — Response to Transmission Limit Violations
Requirement Being Superseded
Superseding BCUC Approved Standard(s)
Requirements R1
EOP-003-2, Requirement 1 (adoption held in abeyance in
B.C. due to PA/PC dependencies)
TOP-001-4
Requirements R2 and R3
TOP-001-4
Requirement R4
TOP-001-4
TOP-002-4
TOP-003-3
20 of 20